Danfoss has published two cybersecurity advisories addressing vulnerabilities in its AK-SM 8xxA, AK-SM 800 and AK-SC 355 product series. Released on November 20, 2026, the advisories identify security risks associated with unauthorized access and potential remote code execution, with CVSS severity scores of 9.3 and 9.9.
The first vulnerability (CVE-2026-129713), with a CVSS score of 9.3, affects Danfoss AK-SM 8xxA controllers running software version 5.4.0 and earlier. A stack-based buffer overflow in an unauthenticated CGI handler can lead to memory corruption, webserver restarts and potentially arbitrary code execution with webserver privileges. Authentication is not required to exploit the vulnerability.
Danfoss plans to address the vulnerability in its upcoming software version 5.5.x and remove the option to disable Strict mode. Until the update becomes available, the company recommends enabling Strict mode, using strong passwords, avoiding public IP exposure and restricting remote access to secure VPNs or protected networks.
The second vulnerability (CVE-2026-127057), with a CVSS score of 9.9, affects all versions of the legacy AK-SC 355 and AK-SM 800 series. Unauthorized access is possible when default credentials or known passwords are used for authentication.
Danfoss recommends upgrading legacy units to the current-generation AK-SM 800A series to ensure continued cybersecurity updates. Additional mitigation measures include removing direct internet exposure, restricting remote access to protected networks and using strong, unique passwords.