STULZ modular cools supercomputer Emmy

STULZ Modular, a subsidiary of STULZ GmbH, has successfully undertaken the task of cooling the "Emmy" supercomputer at the University of Göttingen.

To support the ongoing development of Emmy, the University, alongside GWDG, required a new data center. Existing facilities were inadequate to provide the necessary space and cooling without significant reconstruction. The entire project was designed and delivered within a tight timeframe, completing the installation of a four-room modular data center in less than two months.

Key Results

1. Efficient Supercomputing Solution:
   - 1.5MW of supercomputing capacity is housed within several STULZ micro data centers, delivering 100kW per rack.
   - The 100kW Micro DCs are accommodated in an 85m² modular data center, utilizing direct liquid-to-chip cooling for CPU heat removal and air cooling for other components. This reduces the risk of thermal shutdown and enables processor overclocking for maximum performance.

2. Additional Data Center Space:
   - A secondary 70m² air-cooled STULZ modular data center was constructed to house network and storage equipment, adjacent to the high-density environment.

3. Energy Savings:
   - Compared to a standard air-cooled data center with a PUE of 1.56, the STULZ modular data center offers a 27% electricity savings at an average 75% load, translating to 3.96 GWh annually.

4. Advanced Cooling Technologies:
   - The cooling system captures 78% of high-density heat through liquid and 22% through air.
   - Prefabrication and modular technology ensured quick deployment within the two-month window, leveraging factory-engineered components for faster and more precise onsite work compared to traditional builds.

5. Environmental Impact:
   - Reduced refrigerant usage by up to 80%, significantly lowering Emmy's CO2 footprint.
   - The data center achieved an annual operating PUE of <1.14, aligning with the University's sustainability goals for energy efficiency.

STULZ Modular's swift and effective deployment reflects their expertise in advanced cooling solutions, ensuring Emmy continues to perform at optimal levels while supporting the University's green initiatives.
Related tags: CO2
Share

Related news

RefIndustry Opens Call for Case Studies for Commercial Refrigeratio...
RefIndustry has opened a call for case studies for the upcoming Commercial Refrigeration Special Edition of Refrigeration Industry Magazine, scheduled for publication in February 2026. This...
05 Dec 2025
Nordic Climate Group acquires Huijbregts Koeltechniek in Dutch expa...
Nordic Climate Group has expanded its presence in the Netherlands with the acquisition of Huijbregts Koeltechniek, a refrigeration and climate solutions provider based in Breda. The move aligns wit...
01 Oct 2025
HAUSER to unveil energy-saving cabinets and refrigeration tech at E...
At EuroShop 2026, HAUSER will present new developments in refrigerated cabinets, refrigeration systems and services at stand C35 in Hall 14. Highlights include the REMETA Connect refrigerated cabin...
07 Dec 2025
AREA calls for EU action against illegal refrigerant trade and unce...
The European Association of Refrigeration, Air Conditioning and Heat Pump (RACHP) Contractors (AREA) has issued a position paper warning of gro
today
SWEP heat exchangers integrated into CERN's CO2 cooling upgrade in ...
SWEP brazed plate heat exchangers have been integrated into the next-generation CO2 cooling systems for CERN’s CMS and ATLAS particle detectors, part of the High-Luminosity Large Hadron Collider (H...
yesterday
Shree Refrigerations to Offer Smardt Oil-Free Chillers for Data Cen...
Shree Refrigerations Limited (SRL), a supplier of cooling systems to India’s Defence sector, has entered a strategic association with Smardt Chillers Pte Ltd to deliver oil-free chillers for the co...
12 Sep 2025